021-612 3131 / 0812 9726 3131 cs@platinum-computer.com
Select Page

APC Symmetra PX 64kW Scalable to 96kW 400V with Modular Power Distribution – SY64K96H-PD

gambar APC Symmetra PX 64kW 400V with MPD - SY64K96H-PD

UPS APC SY64K96H-PD

APC Symmetra PX 64kW Scalable to 96kW 400V with Modular Power Distribution
A high-efficiency 3-phase UPS with integrated modular distribution that can be right-sized to your data center power requirements. With scalable power, distribution and run-time, this UPS grows with your data center up to 96kW/96kVA. Suitable for small to medium data centers or individual zones of large data centers.
Includes: Network Management Card , Start-Up Service , User Manual

SY64K96H-PD Features
APC Symmetra PX 64kW Scalable to 96kW 400V with Modular Power Distribution

Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Battery replacement without tools
Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Manageable external batteries
Reduces preventative maintenance service needs by monitoring the health and status of the external batteries and their expected runtime.
Swappable batteries
Allows quick addition of runtime capacity or replacement of existing battery modules. Installed modules are automatically recognized by the system.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)

Symmetra PX Features & Benefits
Marketing Features
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
Network manageable
Provides remote power management of the UPS over the network.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
User-replaceable power modules
Enables simple upgrades and replacements of the Power Modules.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.

Manageability
LED status indicators
Quickly understand unit and power status with visual indicators.
Integrates with StruxureWare Data Center Expert
An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
Audible alarms
Provides notification of changing utility power and UPS power conditions

Total Cost of Ownership
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
5×8 Start-up service included
Required for full coverage of factory warranty
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.

Agility
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
SmartSlot
Customize UPS capabilities with management cards.
Programmable frequency
Ensures compatibility with different input frequencies.

Availability
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
Redundant Intelligence Modules
Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions.
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Network manageable
Provides remote power management of the UPS over the network.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Swappable power modules
Allows quick addition of power capacity or replacement of existing power modules. Installed modules are automatically recognized by the system.

Specifications APC Symmetra PX 64kW Scalable to 96kW 400V with Modular Power Distribution – SY64K96H-PD

Output

Output power capacity

64.0 KWatts / 64.0 kVA

Max Configurable Power (Watts)

96.0 KWatts / 96.0 kVA

Nominal Output Voltage

230V , 400V 3PH

Neutral Output Current

160 A

Output Voltage Note

Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage

Efficiency at Full Load

95.0 %

Output Voltage Distortion

Less than 2%

Output Frequency (sync to mains)

50/60 Hz +/- 3 Hz user adjustable +/- 0.1

Output Frequency (not synced)

50Hz +/- 0.1% for 50Hz nominal

Load Crest Factor

Unlimited

Topology

Double Conversion Online

Waveform type

Sine wave

Overload Operation

10 minutes @ 125% and 60 seconds @ 150%

Output Connections

(1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)

Output Voltage THD

< 2% for 0 to 100% linear load and < 6% for full non linear load

Output Voltage Tolerance

+/-1% static and +/- 5% at 100% load step

Bypass

Built-in Static Bypass

Input

Nominal Input Voltage

400V 3PH

Input frequency

40 – 70 Hz

Input Connections

Hard Wire 5-wire (3PH + N + G)

Input voltage range for main operations

340 – 477 V

Efficiency at Full Load

95.0 %

Input Total Harmonic Distortion

Less than 5% for full load

Maximum Short Circuit Withstand (Icw)

30.0 kAmps

Maximum Input Current

118.0 A

Input Power Factor at Full Load

0.99

Batteries & Runtime

Battery type

VRLA

Included Battery Modules

6

Typical recharge time

3.5 hour(s)

Nominal Battery Voltage

+/-192 V (split battery referenced to neutral)

End of Discharge Maximum Battery Current

221.0 A

Battery Slots Empty

3

RBC Quantity

4

DC Overcurrent Protection

320 A

Extendable Run Time

1

Battery Volt-Amp-Hour Capacity

20736

Extended Run Options

APC-Symmetra-PX-64kW-Scalable-to-96kW-400V-with-Modular-Power-Distribution

End of Discharge Battery Voltage

+/-154 V

Efficiency in Battery Operation

94.0 %

Maximum Available Short Circuit Current

4 kAmps

Overload Operation

60 seconds@ 125% and 30 seconds at 150%

Communications & Management

Interface Port(s)

DB-9 RS-232 , SmartSlot

Control panel

Multi-function LCD status and control console

Audible Alarm

Alarm when on battery : distinctive low battery alarm : configurable delays

Emergency Power Off (EPO)

Yes

Available SmartSlotâ„¢ Interface Quantity

2

Physical

Maximum Height

1991 , 199.1 CM

Maximum Width

1200 , 120.0 CM

Maximum Depth

1070 , 107.0 CM

Rack Height

42 U

Net Weight

1454.0 KG

Shipping weight

1576.0 KG

Shipping Height

2140 , 214.0 CM

Shipping Width

1696 , 169.6 CM

Shipping Depth

1210 , 121.0 CM

Environmental

Operating Environment

0 – 40 °C

Operating Relative Humidity

0 – 95 %

Operating Elevation

0-999.9 meters

Storage Temperature

-15 – 40 °C

Storage Relative Humidity

0 – 95 %

Storage Elevation

0-15000 meters

Audible noise at 1 meter from surface of unit

63.0 dBA

Online thermal dissipation

11496.0 BTU/hr

Protection Class

NEMA 1, IP 20

Conformance

Approvals

EN 50091-1, EN/IEC 62040-1-1, EN/IEC 62040-3, Eurobat General Purpose, FCC Part 15 Class A, ISO 14001, ISO 9001, VFI-SS-111

Standard warranty

1 year on-site repair or replace with factory authorized Start-Up

General

Bypass Connection

5 wire (3PH + N + G)

Bypass Protection Device

160.0

Max Bypass Input Current

139.0 A

Kata Kunci Terkait :