021-612 3131 / 0812 9726 3131 cs@platinum-computer.com
Select Page

Gambar PRO9010-WRS/WRL 10KVA

UPS PROLINK  Professional II (1P/1P) Rack

Prolink Professional II Series (1P/1P) Rack/Tower is a single-phase UPS system using microprocessor controlled true online double conversion technology and it can be used to provide protection for critical loads especially on IT applications. High input power factor correction in the system improves efficiency and reduces overall losses. Users can easily monitor and access to their UPS status from a comprehensive LCD display. Both Tower and Rack Types of UPS systems have USB and RS-232 communication ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relay contact cards. SNMP option is also available for power management via SNMP manager and web browser. In addition, Emergency Power Off (EPO) function is also available to protect the personnel and the equipment in case of fire outbreak or other types of emergency

Key Features
• True double-conversion
• Microprocessor control optimizes reliability
• Input power factor correction
• Output power factor 0.8
• Wide input voltage (110 V – 300 V)
• Converter mode available
• ECO mode for energy saving (Only available for 1-3KVA model)
• Generator compatible
• Smart SNMP works well with either USB or RS-232 together
• Emergency power off function (EPO)
• Optional isolation transformer available

Rear Panel
1. AC input
2. Input circuit breaker
3. USB communication port
4. RS-232 communication port
5. Intelligent slot
6. External battery connection (only available for L model)
7. Output receptacles
8. Output terminal

6-10KVA
1. External battery connector
2. RS-232 communication port
3. Intelligent slot
4. USB communication port
5. Emergency power o function connector (EPO connector)
6. Input circuit breaker
7. Input/Output terminal

SPECIFICATIONS PRO910-WRS/WRL 10KVA

GENERAL
UPS Type : Rack / Tower
Phase : Single phase with ground
Rating (VA) : 10000
Nominal Power (W) : 8000
Standard Model Dimension (mm) : UPS Unit: 580 x 438 x 133 [3U] (D x W x H) Battery Pack: 580 x 438 x 133 [3U] (D x W x H)
Weight (kg) : UPS Unit : 18 Battery Pack : 51
Long-run Model Dimension (mm) : 530 x 438 x 133 [3U] (W x D x H)
Weight (kg) : 18

INPUT
Connection Type : Terminal
Nominal Voltage : 208/220/230/240 VAC
Voltage Range : 110-300 VAC ± 3% at 50% Load 176-300 VAC ± 3% at 100% Load
Frequency Range : 46Hz ~ 54 Hz or 56Hz ~ 64 Hz
Power Factor : ≥ 0.99

OUTPUT
Connection Type : Terminal
Nominal Voltage : 208/220/230/240 VAC
Voltage Regulation : ±1%
Frequency Range (Synchronized Range) : 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) : 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio : 3:1
Harmonic Distortion : ≤3% THD (Linear load) ≤5% THD (Non-linear load)

ALARM & INDICATORS
Battery Mode : Sounding every 4 seconds
Low Battery : Sounding every second
Overload : Sounding twice every second
Fault : Continuously sounding
LCD : Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING
Front panel : Status LED, Function keys, LCD display
Communication : Smart RS232* USB Port Emergency Power Off (EPO)

BATTERY
Standard Model Type : 12V / 9Ah
Numbers : 16
Typical Recharge Time : 9 hours recover to 90% capacity
Long-run Model Type : Depending on the capacity of external batteries
Number : 16 – 20 pcs (Adjustable)
Charging Current (max) : 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)

REAR PANEL
1. External battery connector
2. RS-232 communication port
3. Intelligent slow
4. USB Communication port
5. Emergency power off function connector (EPO connector)
6. Input circuit breaker
7. Input/output terminal

×

Platinum-Computer.Com