APC Easy UPS On-Line SRV 2000VA 230V Extended Runtime Model, No Battery
SRVPM2KIL :
Key Features SRVPM2KIL
-Run time for load Min-max: 160-1600 W 1600 W —
-Max. Capacity Used : 100%
-Output power capacity : 1.6kWatts / 2.0kVA
-Output Connections : (4) IEC 60320 C13 (Battery Backup)
-Nominal Output Voltage : 230V
-Nominal Input Voltage : 230V
-Input Connections : IEC 60320 C14
APC Easy UPS On-Line SRV 2000VA 230V Extended Runtime Model, No Battery
-High quality, Double-conversion On-line UPS designed for essential power protection needs even in the most unstable power conditions.
-Includes: CD with software, USB cable, User manual
Automatic internal bypass
Pure static bypass switch without bridging contactor securing a fast and reliable transfer to and from bypass, rated for 125% nominal load.
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Intelligent Card Slot
Mini slot supports various optional management cards which provide basic or essential monitoring, management and control features for the UPS.
LCD display
Manage the UPS locally through a text-based display that allows quick diagnosis via stored alarm conditions and events.
Serial connectivity
Provides management of the UPS via a serial port.
USB connectivity
Provides management of the UPS via a USB port (not available on all models).
Easy UPS On-Line Features & Benefits
Availability
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Features
Double conversion on-line topology
Guarantees a consistently high level of power quality. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.
Allows the user to manage the UPS functions, schedule automatic shutdown and monitor the power grid occurrences through an interactive interface that ensures an easy and intuitive monitoring.
Management Software
Generator compatible-
Ensures clean, uninterrupted power to protected equipment when generator power is used.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
High efficiency
High efficiency rates that remain stable even at lower operating power levels
Management Software
Allows you to easily monitor your utility power and manage your UPS.
Intuitive LCD interface
Provides clear and accurate information in multiple languages with the ability to configure the UPS locally with easy to use navigation keys.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Pure sine wave output on battery
Simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.
Manageability
Serial connectivity
Provides management of the UPS via a serial port.
Network manageable
Most models provide remote power management options of the UPS over the network. Many do not have NMC embedded.
Intelligent Card Slot
Customize UPS capabilities with management cards.
LED Indicators
Provide easy-to-read status of the unit and utility power conditions.
LCD graphics display
Text and mimic diagrams that display modes of operation, system parameters and alarms.
Serviceability
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Audible alarms
Provides notification of changing utility power and UPS power conditions
Predictive failure notification.
Provides early-warning fault analysis ensuring proactive component replacement.
Disconnected battery notification
Warns when a battery is not available to provide backup power.
Technical Specifications
Output | ||
Max Configurable Power (Watts) | : | 1.6kWatts / 2.0kVA |
Output Voltage Distortion | : | 3 % |
Output Frequency (sync to mains) | : | 50/60 Hz +/- 3 Hz Sync to mains |
Other Output Voltages | : | 220 V, 240 V |
Load Crest Factor | : | 3 : 1 |
Topology | : | Double conversion online |
Waveform type | : | Sine wave |
Bypass | : | Internal bypass (automatic and manual) |
Input | ||
Input frequency | : | 40 – 70 Hz Auto sensing |
Input voltage range for main operations : | : | 110 – 285 Half load, 160 – 280 Full loadV |
Number of Power Cords | : | 1 |
Other Input Voltages | : | 220 V, 240 V |
Batteries & Runtime | ||
Battery type | : | Lead-acid battery |
Nominal Battery Voltage | : | 72 V |
Efficiency | : | View Efficiency Graph |
Communications & Management | ||
Interface Port(s) | : | USB |
Control panel | : | Multifunction LCD status and control console |
Audible Alarm | : | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
Surge Protection and Filtering | ||
Surge energy rating | : | 600Joules |
Physical | ||
Maximum Height | : | 238MM, 23.8CM |
Maximum Width | : | 145MM, 14.5CM |
Maximum Depth | : | 400MM, 40.0CM |
Net Weight | : | 16.8KG |
Shipping weight | : | 9.1KG |
Shipping Height | : | 330MM, 33.0CM |
Shipping Width | : | 235MM, 23.5CM |
Environmental | ||
Operating Temperature | : | 0 – 40 °C |
Operating Relative Humidity | : | 0 – 95 (Non-condensing) % |
Operating Elevation | : | 0 – 3000meters |
Storage Temperature | : | -20 – 50 °C |
Storage Relative Humidity | : | 0 – 95 (Non-condensing) % |
Storage Elevation | : | 0 – 15000meters |
Audible noise at 1 meter from surface of unit | : | 50.0dBA |
Conformance | ||
Approvals | : | CE, EAC, EN/IEC 62040-1, EN/IEC 62040-2 |
Standard warranty | : | 2 years repair or replace |