021-612 3131 / 0812 9726 3131 cs@platinum-computer.com
Select Page

Daker DK Plus 3 101 70 Single phase VFI – 1000 VA – 900 W

Gambar Daker DK Plus 3 101 70 Single phase VFI - 1000 VA - 900 W

PRODUCT DESCRIPTION

Product characteristics
Convertible UPS with batteries Single phase
– The stated backup time in minutes is estimated and may vary according to the load characteristics, operating conditions and environment
– Nominal power: : 1000 VA
– Active power: : 900 W
– Backup time: : 9 min
– Weight: : 16 kg

General characteristics
DAKER DK PLUS – On-line double conversion UPS (rack/tower) – single phase and three phase VFI
– The main parameters of the UPS, including the battery charge level and faults, are displayed on the LCD screen on the front panel
– The integrated communication software not only controls the UPS and its switch-off if there is a malfunction, and enables the user to test the main functions remotely, communicate via SNMP/Internet/network adaptor and access the functions of the UPS via the Internet, but can also send the user an SMS if specific events occur
– The internal extension connector enables aWEB/SNMP card or a relay interface to be installed which provides insulated contacts for applications on industrial control panels or remote alarm panels
– If there is an electronic fault, overload, overheating or for scheduled maintenance operations, the automatic or manual (optional) bypass ensures continuity of the power supply for critical loads. A bypass switch is available for maintenance

Spesifikasi UPS Daker DK Plus 3 101 70

General
– Nominal power (VA) : 1000
– Active power (W) : 900
– Technology : On-line double conversion VFI-SS-111
– Waveform : Sinusoidal
– Architecture : Convertible tower and 19″ rack
– Surge Rating : 1145
– ECO Mode efficiency : %97

Input
– Input voltage : 230 V
– Input frequency : 50-60 Hz ± 5% autosensing
– Input voltage range : 180 V – 300 V at full load
– THD of input current : < 3%
– Input power factor : > 0,99
– Input Plug : 3 101 70: Multi Standard, 3 100 49: British Standard

Output
– Output voltage : 230 V ± 1%
– Output frequency (nominal) : 50/60 Hz (configurable via LCD panel) +/- 0.1%
– Efficiency up to : 90%
– Peak factor : 1:3
– THD of output voltage : Linear load 2% Nonlinear load 5%
– Output voltage tolerance : ± 1%
– Bypass : Internal automatic Bypass (included) External maintenance Bypass (OPTIONAL)

Batteries
– Uptime Expansion : yes
– Number of batteries : 3
– Battery series Type/Voltage : 12V 7.2Ah
– Uptime with 80% load (min) : 10
– Recharge time (to 100%) : 4 hours
– Battery disconnector for safe transportation : yes

Communication and management
– Display and Signals : Four buttons and four LEDs to monitor the status of the UPS in real time
– Communication Ports : RS232 serial ports, USB
– Remote Management : available
– Network interface slot : SNMP

Mechanical features
– Measurements H x L x D (mm) : 440×88 (2U) x405
– Battery Cabinet Measurements H x L x D (mm) : 440×88 (2U) x425
– Net Weight (kg) : 16

Environmental conditions
– Operating temperature (°C) : 0 ÷ 40 °C
– Degree of protection : IP20
– Relative humidity (%) : 0-95% non-condensing
– Noise level at 1 m (dBA) : On-Line Mode < 50, Eco Mode < 40
– Heat Loss (BTU/h) : 490

Certifications
Standards : EN 62040-1, EN 62040-2, EN 62040-3

×

Platinum-Computer.Com