021-612 3131 / 0812 9726 3131 cs@platinum-computer.com
Select Page

Keor T Evo on-line double conversion UPS 

Three phase VFI SS 111 – 10 kW – backup time 10 min
#3 102 71

Gambar Legrand Keor T Evo on-line double conversion UPS (3 102 71)

 

PRODUCT DESCRIPTION

Product characteristics
UPS
• Nominal power: : 10 kW
– Backup time: : 10 min
– Dimensions (H x W x D): : 1020 x 265 x 800 mm
– Net weight: : 145 kg

General characteristics

KEOR T EVO – On-line double conversion UPS (tower) – three phase VFI SS 111
– For civil, commercial, industrial automation and IT applications requiring small three phase power (up to 20 kVA) with standard back up time in compact footprint
– Installation: downstream power generators. 3 level IGBT inverter
– DSP advanced control logic
– Power factor: 1 (kVA = kW). Efficiency up to 95%
– Internal Batteries
– Touch Screen Display
– Parallel connection possible: up to 4 UPSs. Dedicated input bypass line. Embedded manual bypass
– Full connectivity with RS232, RS485 (ModBus), 4xDry contacts, Net Interface Slot (SNMP), EPO, Generator Friendly port
– Equipped with wheels for easy moving of the UPS

 

specifications UPS Legrand (3 102 71)

General specifications
• UPS Topology : On line double conversion VFI SS 111
• Architecture of the UPS : Stand alone, transformerless, On-Site Paralleling
• In/Out phase Configuration : Three phase-Three phase
• Neutral : Neutral Passing through
• Switching Technology : 3-Level IGBT
• Backfeed Protection : Internal, standard
• Output wave form on mains operation : Sinusoidal
• Output wave form on battery operation : Sinusoidal
• Standards : EN 62040-1, EN 62040-2, EN 62040-3

Input
• Nominal Voltage : 400 3ph+N+PE
• Voltage Range : 358 – 459 Ph-Ph full load, 208 – 459 Ph-Ph half load”
• Frequency : 45 – 65Hz
• THDin : < 5% at full load
• Power Factor : > 0.99

Bypass
• Nominal Voltage : 400 3ph+N+PE
• Voltage Range : 380/400/415V -18% +15% (adjustable)
• Frequency : 47-53Hz or 57-63Hz (adjustable)
• Bypass Type : Static and Electro-mechanic
• Transfer Time : Zero
• Manual Bypass : Built-in

Output with mains (AC-AC)
• Nominal Voltage : 380, 400, 415 3ph+N+PE
• Nominal Power : 10.000 VA
• Active Power : 10.000 W
• Voltage variation (static) : ± 1%
• THDv on nominal power (linear load) : < 2%
• THDv on nominal power (non-linear load) : < 4%
• Frequency : 50 Hz or 60 Hz (selectable)
• Frequency tolerance : ± 0,1% Synchronized with input frequency
• Current Crest Factor : 2.5:1 accordingly to IEC 62040-3
• Overload capability :
– 10 min 125% load with no bypass
– 60 sec 150% load with no bypass

Output on battery (DC-AC)
• Nominal Voltage : 380, 400, 415 3ph+N+PE
• Nominal Power : 10.000 VA
• Active Power : 10.000 W
• Voltage variation (static) ± : 1%
• THDv on nominal power (linear load) : < 2%
• THDv on nominal power (non-linear load) : < 4%
• Frequency : 50 Hz or 60 Hz (selectable)
• Frequency tolerance : ± 0,01% free run
• Current Crest Factor : 2.5:1 accordingly to IEC 62040-3
• Overload capability:
– 10 min : 125%
– 60 sec : 150%

Battery
• Type : Lead Acid, sealed, free maintenance VRLA
• Unit Capacity : 7 or 9 Ah (12V)
• Nominal UPS Battery Voltage : ±144 Vdc (max ±192 Vdc)
• Nominal n. of possible internal battery : 24pcs (12×2)
• Max. n. of possible internal battery : 32pcs (16×2)
• Battery charger type : IGBT Rectifier also charges batteries
• Charging Cycle : Intelligent with boost charge and advanced management”
• Max Charging Current without derating : 2 A

Environmental specs
• Noise level @ 1m (50% load) : < 51dBA
• Operating temperature range : from 0°C to +40°C
• Stock temperature range : from -20°C to +50°C
• Humidity range : 20-95% not condensing
• Protection degree : IP20

Mechanical and miscellaneous
• Net Weight without batteries ¹ : 78 kg
• Dimensions (HxW xD) : 102 0x 265 x 800 mm
• Colour : Enclosure: RAL 7016Front Door Metal: RAL 9005
• Communication Interface : 1 serial port RS232, 1 RS485, 1 smart port for internal SNMP, 4 Dry Contacts, 1 EPO, 1 GENSET
• Input/Output connections : 3Ph + N + PE

 

×