Promo Harga Autocad LT 2017 - Menyambut Awal Tahun 2017
 Categories : UPS SOCOMEC

 

Socomec DELPHYS EM Elite

gambar delphys-em-elite

UPS DELPHYS EM Elite

The EMergency CPSS range has been designed to answer your needs in terms of power supply for your safety system.
All our EMergency products are compliant with standard EN 50171.
The EMergency CPSS products are intended to ensure energy supply to emergency escape lighting in the event of main supply failure. Depending on the local legislation, it may be suitable for energizing other essential safety equipment, such as:
• electric circuits of automatic fire extinguishing installations;
• paging systems and signaling safety installations;
• smoke extraction equipment;
• carbon monoxide warning systems;
• special safety installations related to specific buildings, e.g. high-risk areas.

The wide range fits all standard needs. For the non-standard request, our expert team will be at your service to adapt the products to your needs.

The solution for
• Airports
• Railways and bus stations
• Schools and universities
• Hospitals
• Shopping centers
• Cinemas and theatres
• Museums
• Public buildings
• Office buildings
• Hotels

Standard features
• IP20 metal enclosure compliant with EN60598-1.
• Battery charging: 80% in 12 hours.
• Battery protection against the damage due to a polarity inversion.
• Battery protection against deep discharge.
• Long life battery with 10 year-life expectancy.
• Designed to withstand 120% of the nominal charge during the entire back-up period.
• Specific dry contacts & monitoring for EMergency system

Options
• Transformer embedded in the UPS enclosure (contact us for further information)
• Connection to downstream IT earthing system
• Eco mode to reach up to 98% of efficiency
• Other types battery available

Specifications UPS Socomec DELPHYS EM Elite

Sn [VA]10152030406080up to 500
Pn [W]913.51827364864contact us
Pn according to EN 50171 [kW]7.511.31522.5304053.5
Input / output (3/1)
Input / output (3/3)
Input
Rated voltage400 V (3ph+N)contact us
Voltage tolerance (1)± 20 %
Rated frequency50 – 60 Hz
Frequency tolerance± 10 %
Power factor / THDI> 0.99 / < 3 %
Output
Rated voltage230 V (1ph+N) – 400 V (3ph+N)contact us
Voltage tolerance± 1 %
Rated frequency50 – 60 Hz
Frequency tolerance± 0.01%
Overload UPS designed125% for 10 min, 150% for 1 min
Crest factor3:1
Total voltage distortion – linear load1 %
UPS Cabinet
Dimensions W x D x H (mm)444x795x1400contact us
Maximum weight (kg) with embedded battery515
Maximum weight (kg) without battery120124127138158201211
Protection degreeIP 20 (EN 50171)
Acoustic level (dBA) 1m (ISO 3756)< 62
Battery
TypeVRLA with 10 years-life expectancycontact us
Standard back up time at the end of battery life60/90/120 min (1)
Charging capabillity80 % of the autonomy in 12h
External battery
Standards
CPSSEN 50181contact us
SafetyEN 62040-1; EN 60950-1
EMCEN 62040-2
PerformanceEN 62040-3 (VFI-SS-111)
Product declarationCE

(1) Condition apply

Kata Kunci Terkait :

DELPHYS EM Elite, ups Delphys EM Elite, jual ups Delphys EM Elite, harga ups Delphys EM Elite, spesifikasi ups Delphys EM Elite, beli ups Delphys EM Elite, ups socomec