021-612 3131 / 0812 9726 3131 cs@platinum-computer.com
Select Page

Vertiv Liebert EXL S1 UPS 300-1250 kW

Liebert® EXL S1 menghadirkan daya yang aman sekaligus memberikan perlindungan beban kelas satu dan penghematan energi maksimum untuk pusat data menengah-besar dan aplikasi misi penting.

Specifications  Vertiv Liebert EXL S1

Ratings (kVA ) 300 400
Input
Nominal mains input voltage / voltage range* (V) 400 (200 to 460), 3Ph or 3Ph + N
Nominal bypass input voltage / voltage range* (V) 400 (380/415 selectable), 3Ph or 3Ph + N
Nominal frequency / frequency tolerance (Hz) 50±10%(60 selectable)
Input Power Factor ≥ 0.99
Input current distortion (THDi) (%) ≤3
Output
Nominal output voltage (V) 400 (380/415 selectable), 3Ph or 3Ph + N
Nominal output frequency (Hz) 50 (60 selectable)
Output voltage stability by load variation 0-100% (%)

  • static
  • dynami
±1
Complies with IEC/EN 62040-3, Class 1
Output frequency stability

  • synchronized with bypass mains (%)
  • synchronized with internal clock (%)
±2 (2, 3, 4, 5 selectable)
±0.1
Inverter Overload Capacity* 110% continuous, 125% for 10mins, 150% for 1min
Output PF* up to 1
Load crest factor handled without derating the ups (Ipk/Irms) 3:1
Compatibility with loads Any power factor (leading or lagging) up to 1
Battery
Permissible battery voltage range (V) 396 to 700
Float voltage for VRLA @ 20 °C (V/cell) 2,27
End cell voltage for VRLA (V/cell) 1.65
Float Voltage stability in steady state condition (%) ≤1
DC ripple voltage without battery (%) ≤1
Battery Switch Not included
Bypass
Manual Maintenance Bypass Included 100-500 kW
General and system data
Classification according to IEC/EN 62040-3 VFI-SS-111
Operating Temperature (°C) 0-40
Maximum relative humidity @ 20 °C (non condensing) (%) up to 95
Protection degree with open doors IP 20
Frame colour (RAL scale) 7021
Noise @ 1 metre as per ISO 3746 (dBA ± 2dBA) 69
65 dBA @partial load
Parallel configuration up to 8 units in paralle
Access Front and Top (no rear access required)
AC/AC efficiency:

  • VFI according to IEC/EN 62040 definition (%)
  • VFD according to IEC/EN 62040 definition (%)
up to 97%
up to 99%
Dimension and weight 
Height (mm) 1950
Width (mm) 1000
Depth (mm) 900
Net Weight (kg) 725
Conditions apply
×