UPS online konversi ganda Vertiv™ Liebert® GXT5 Lithium-Ion memberikan pengkondisian daya dan perlindungan daya tingkat tertinggi untuk sistem TI bisnis penting seperti peralatan jaringan dan server bisnis. Hal ini memastikan bahwa sistem dan aplikasi penting Anda terlindungi jika terjadi masalah daya utilitas seperti lonjakan daya atau pemadaman listrik total. UPS Liebert® GXT5 melindungi terhadap berbagai masalah daya dan dengan mudah beralih ke cadangan baterai jika kualitas daya input berada di luar tingkat pengoperasian yang dapat diterima.

Specifications Vertiv Liebert GXT5, 5-6 kVA

Standard Models GXT5LI-5000GVRT3UXLN GXT5LI-6000GVRT3UXLN
Form Factor 3U Rack/Tower
Power Rating 5000 VA / 5000 W 6000 VA / 6000 W
Dimensions, W x D x H, mm (in)
Unit 430 x 890 x 133
(16.9 x 35 x 5.25 (3U)
430 x 890 x 133
(16.9 x 35 x 5.25 (3U)
Shipping 798 x 998 x 532 (31.4 x 39.3 x 20.9)
Weight, Kg (Lb) 
Unit with EBCs* 45 (99) 99 (45)
Unit without EBCs 23 (51) 23 (51)
Shipping 72 (159) 72 (159)
Input/Output AC Parameters
Input Plug Hardwired (L1-N/L2-G) Hardwired (L1-N/L2-G)
Output Hardwired (L1-N/L2-G) Hardwired (L1-N/L2-G)
Nominal Voltage Setting 230VAC (Default); 200-240VAC (User-Configurable); ±1%
Voltage Range Without Battery Operation Nominal (Full Load): 176V – 288V AC; Maximum: 100 – 288VAC
Frequency Range 40~70Hz
Surge Protection IEC 61000-4-5, ANSI C62.41, Category B
Transfer Time 0 ms
Battery Waveform Pure Sine Wave
Battery Parameters 
Type Lithium-Ion (LiFePO4)
Recharge Time (from full discharge) < 2hrs to 90% < 2hrs to 90%
Full-Load Runtime 11 min 9 min
Half-Load Runtime 25 min 25 min
Replacement Battery N/A, external battery only N/A, external battery only
External Battery Cabinet (quantity) VEBCLI-192VRT1U (1) VEBCLI-192VRT1U (1)
Environmental Requirements 
Operating Temperature, °C (°F) 0°C to 40°C (32°F to 104°F) (10% Derating at 50°C)
Storage Temperature °C (°F) -20° to 60° (-4° to 140° )
Relative Humidity 0% – 95%, non-condensing
Operating Altitude, m (ft) 0 to 3,000 (0 to 10,000) w/o Derating (15% Derating at 4000m)
Audible Noise < 58 dB
Certifications
Safety IEC 62040-1:2008+A1 2013, IEC 62619 1st Ed., UL 1642 (Li-Ion Battery Cells), UL 1973 (Li-Ion Battery Pack w/UPS), UL 1778, CSA 22.2 No. 107.3
Agency IEC 62040-1:2008+A1 2013, IEC 62619 1st Ed., IEC 62040-2 2nd Ed., IEC 61000-3-2, IEC 61000-3-12, CISPR22, Class A, FCC Part 15, Class A, UL 1778
Environmental RoHS2 / REACH / WEEE
Network Surge IEC 61000-4-5, ANSI C62.41, Category B
Transportation ISTA Procedure 2A
Warranty 5 years on UPS and Battery

 

×